Page 51 - CE JOURNAL FEB 2024 ISSUE 20
P. 51

TECHNICAL ASSESSMENT
                   MATLAB Simulink models were developed and used for simulation analysis. Some examples of the models
                   developed are as follows:






















                                       Simulink Model for DC-AC Bi-Directional Inverter with Voltage Stability Control




















                                  Simulink Model for 158kW Array with Irradiance Table based on Sun Path Chart and Satellite Data.



















                                          Figure 6: Simulink Model for T&TEC Grid up to customer for case study

                   The BESS was developed from the calculated 10-day autonomy and the market research information. A
                   Constant Current/Constant Voltage (CCCV) battery charging module was developed and another DC-DC
                   bi-directional converter was used to step up battery output to the 776V required DC bus level. Discrete
                   Proportional Integral Differential (PID) and Proportional Integral (PI) controllers were implemented for charge
                   and discharge control about 80% SOC.



                                                                                                           51