Page 37 - CE_Industral_Journal_2014
P. 37

and  test  injection  is  compact  and  lightweight  for  easy   MEASURING THE CT DATA
        commissioning use.                                      The electrical data of the CT are assessed with the CT
                                                                Analyzer  device  in  a  similar  fashion.  The  CT  -  burden
        The benefits of this ‘virtual primary injection test’ are the   circuit stays interrupted and the analyzer is connected to
        greatly  increased  knowledge  and  resulting  trust  in  the   the CT (see Fig. 3).
        actual  worst-case  relay  behaviour  as  affected  by  the
        conditions on site. The commissioning staff will know if the
        possibly unavoidable CT saturation will be acceptable with
        regards to the relay performance, or if additional measures
        have to be taken.

        This approach is valid for distance protection as well as for
        overcurrent protection. It is also applicable for differential
        protection in order to verify the proper settings of stabilizing
        functions against false tripping due to CT saturation.


        MEASURING THE ACTUAL CT BURDEN
        For  the  measurement  of  actual  burden,  the  secondary      Fig. 3: Connection for CT measurement
        circuit of the CT is disconnected at the CT terminal and
        the burden circuit is connected to the CT Analyzer [2] as   The  underlying  CT  model  considers  nonlinear  real  and
        shown in Fig. 2.                                        inductive  impedance  components  and  remanence  to
                                                                properly evaluate the CT data (see Fig. 4).











                                                                            Fig. 4: CT model in CT Analyzer


                                                                The data from the burden and CT measurements may be
                                                                saved as XML file for subsequent use by the test system.


                                                                SELECTION OF THE TEST CASES FOR SIMULATION
               Fig.2: Connection for burden measurement         For  all  simulations  in  question  a  portable  and  simplified
                                                                simulation  package  can  be  used,  with  CT  saturation
        In this way the full external burden (including cables and   simulation  capability  being  indispensable.  Grid  data  is
        relay input curcuit) is included in the measurement, the CT   needed for the physically correct calculation of transient
        analyzer injecting the test current with one pair of terminals   fault  quantities.  The  time  constant  of  the  decaying  DC
        and assessing the voltage drop with a second pair. The   component  should  result  from  the  complex  impedance
        result is a complex impedance. Its angle, though usually   values of the grid. The calculated transient primary currents
        fairly small, substantially influences the transient saturation   are passed through the CT simulation by using the burden
        devolution  and  should  be  taken  into  account  for  the   and CT data from the measurements, resulting in realistic
        subsequent simulation.                                  secondary currents. In this way the relay is exposed to
                                                                test signals that closely relate to secondary currents that
        It  must  be  noted  that  a  precondition  for  this  simulation   would have been achieved by primary short-circuit tests.
        approach is the linearity of the system under investigation,
        i.e.  the  burden  should  not  change  its  impedance  with   The following time signal view shows a sample of such a
        varying injected current. Cables and current input circuits   simulation that clearly shows the saturation effect of the
        of  relays  with  auxiliary  power  supply  (e.g.  numerical)   CT model in the simulation (see Fig. 5).
        fulfill this requirement, but this is not necessarily true for
        electromechanical and other self-powered relays.

                                                                                                  INDUSTRY JOURNAL 35
   32   33   34   35   36   37   38   39   40   41   42